Modular technology, suitable for all brand and model batteries, with high system efficiency
Bidirectional high-frequency isolation, extremely high safety
Highly integrated, fully built-in lithium battery, BMS, PCS, monitoring, and fire protection
Intelligent management of battery clusters, meeting diverse loads, and long service life
Standardized cabinet, easy transportation and installation
en
Technical Parameter | JWB10-E240 | JWB20-E720 | JWB40-E1440 | JWBHW-E120 | |
Battery Parameters | |||||
Rated Battery Capacity | 240kWh | 720kWh | 1440kWh | 120kWh | |
Rated power at DC side | 120kW | 360kW | 720kW | 60kW | |
Electric Box Model | JWP-280-1P16S | ||||
Battery Voltage Range | 200~750V | ||||
BMS Communication Interface | RS485, CAN2.0, Ethernet | ||||
System Parameter | |||||
Box Size(L×D×H) | 2991×2438×2896mm | 6058×2438×2896mm | 12192×2438×2896mm | 2480×900×2400mm | |
Box Weight (Including Battery) | 7t | 14t | 30t | 4t | |
Protection Level | IP54 | ||||
AC Current Distortion Rate | <3%(At Rated Power) | ||||
DC Component | <0.5%(At Rated Power) | ||||
Rated voltage at AC side | 380V | ||||
Rated frequency of power grid | 50Hz | ||||
Power Factor | >0.99(At rated power) | ||||
Isolation method | High frequency isolation | ||||
Operating temperature range | -20~50℃ | ||||
Operating humidity range | 0~95%(Non-condensing) | ||||
Maximum working altitude | 3000m(>Derating required for 2000m) | ||||
Battery temperature control mode | Industrial grade temperature controlled air conditioning | ||||
Fire protection system | Heptafluoropropane fire protection | ||||
System communication protocol | Modbus TCP | ||||
System communication interface | RS485, Ethernet |