Bidirectional high-frequency isolation technology, leading in China
High efficiency, power density up to international advanced level
Wide constant power range and strong adaptability
High performance DSP chip for real-time monitoring
Complete fault protection functions and convenient maintenance
Rectification mode parameters | |
Rated output power | 20KW |
Grid side voltage | 380Vac ± 15% (three-phase) |
Grid frequency | 50Hz±5Hz |
DC side output voltage | 200~750Vdc |
DC side output current | 50Amax |
Inverter mode parameters | |
DC side input voltage | 200~750Vdc |
DC side input current | 50Amax |
Grid side voltage | 380Vac (three-phase) |
Grid frequency | 50Hz±5Hz |
System Parameter | |
Working Temperature | -20 ℃~50 ℃ (derate the output if it exceeds 50 ℃, and shut down if it exceeds 70 ℃) |
Height | ≤ 2000m (over 2000m, derate according to GB/T3859.2) |
Relative humidity | 5%~95% |
Maximum efficiency | 94% |
Power factor | ± 0.99 (full load) |
THDI | <5% (full load) |
Voltage stabilization accuracy | <±0.5% |
Steady current accuracy | <±1% |
Output voltage setting error | <±0.5% |
Output current setting error | <±1% |
Start input impulse current | ≤ 110% of rated input current |
Voltage limiting characteristics | During steady current operation, if the DC output voltage exceeds the set value, the increase in output voltage is automatically limited and the state is switched to steady state |
Current limiting characteristics | During steady state operation, if the DC output current exceeds the set value, the increase in output current is automatically limited and the state is switched to steady state |
Wiring mode | 3P3W |
Installation method | Rack |
Protection level | IP21 |
Cooling method | Forced air cooling (forward air, rear air outlet) |
Noise | ≤65dB |
Communication method | CAN |